The cable tray system shall be provided with reliable electrical continuity and earthing (applicable to metal cable trays only).

If the cable tray system is permitted to serve as an earth conductor circuit, the following requirements shall be met: the resistance of electrical connections between tray sections shall not exceed 0.035 Ω. In TN-S or TN-C-S systems, where the earth of the consumer installation and the system neutral are earthed and equipped with automatic power cut-off devices, the cross-sectional area of the metal tray along its longitudinal direction shall not be less than the specified value.

Where a separate earthing main conductor is laid along the full length of the cable tray, each tray section (including non-straight sections) shall be reliably connected to the earthing main conductor at no less than one point.

For locations subject to vibration, spring washers shall be fitted at earthing connection joints.